PDU Power & Breaker Calculator
From vendor documentationTurn a rack load in watts into line current for single- or three-phase feeds, apply the 80 % continuous derating, pick the next standard breaker size and count the C13 and C19 receptacles the load needs.
Input
Real power drawn by everything in the rack. Every watt becomes heat.
Three phase takes the line-to-line voltage: 400 V for 230/400 V, 208 V for 120/208 V. Single phase takes the line-to-neutral voltage: 230 V or 120 V.
Real power ÷ apparent power. Defaults to 0.95; lower draws more current, so 0.9 is the conservative choice.
Export
The calculation and the device breakdown
Line current
7,150 W at 400 V three phase (line-to-line)
- Line current
- 10.86 A
- Apparent power
- 7.53 kVA
- Derated working current
- 13.58 A
Per line conductor.
Real power ÷ power factor 0.95
10.86 A ÷ 0.8 — the rating the device must have before rounding.
I = P / (√3 × V_LL × PF) = 7150 W / (1.7321 × 400 V × 0.95) = 10.86 A
Recommended breaker
- Breaker rating
- 16 A
- Continuous headroom
- 12.80 A
Next standard size at or above the derated current.
80 % of a 16 A device.
How this was chosen
PDU and receptacles
- IEC C13 outlets
- 2
- IEC C19 outlets
- 1
- C13 working limit
- 8 A
- C19 working limit
- 12.8 A
Rated 10 A, working 8 A each.
Rated 16 A, working 12.8 A each.
10 A rating × 0.8.
16 A rating × 0.8.
Receptacle count is a minimum, not a BOM
Conventions and assumptions
What is a rule, and what is a choice
- 80 % continuous derating (rule). A device carrying a load for three hours or more must not exceed 80 % of its rating, so the derated current is amps ÷ 0.8 and the breaker rounds up from there (NEC 210.19(A)(1), 210.20(A)).
- Standard breaker list (convention). The sizes offered are the IEC 60898-1 / IEC 60364-4-43 preferred values up to 63 A plus the common North American 80 A, 100 A and 125 A. NEC 240.6(A) also lists 15 A, 35 A, 45 A and 60 A, which are rare on rack PDUs.
- Power factor (convention). The default is 0.95, where modern 80 PLUS Gold and Titanium supplies are typically rated. A lower power factor draws more current, so 0.9 is the conservative choice when the nameplate data is unknown.
- IEC 60320 ratings (rule). C13 is rated 10 A and C19 16 A; the working figures shown are those ratings after the 80 % derating.
- C13/C19 split (convention). Outlet counts assume 25 % of the load lands on C19 receptacles and the rest on C13. The number reported is the minimum that carries the load, not a recommended BOM.
Frequently asked
- Why is the derated current higher than the load current?
- Because a breaker must not carry more than 80 % of its rating continuously (NEC 210.20(A)). A 12 A continuous load therefore needs a 12 ÷ 0.8 = 15 A device, which rounds up to the next standard size of 16 A — not 12 × 0.8 = 9.6 A.
- Which voltage do I enter for a three-phase feed?
- The line-to-line voltage — 400 V for a European 230/400 V supply, 208 V for a North American 120/208 V supply. The formula divides by √3 × V, so entering the phase-to-neutral voltage would overstate the current by a factor of √3.
- What power factor should I use?
- 0.95 if you do not know, which is where modern 80 PLUS Gold and Titanium supplies are typically rated. A lower power factor draws more current for the same real power, so 0.9 is the more conservative assumption; a measured figure always beats both.
- How many C13 and C19 outlets does my rack need?
- The tool reports the minimum receptacles that can carry the load at the derated per-outlet rating, assuming 25 % of the load lands on C19 (16 A) receptacles and the rest on C13 (10 A). Feed it your real bill of materials for an exact count.
- Is the calculation sent anywhere?
- No. Every figure is computed in your browser and the page makes no network requests.
Next
- BTU & Cooling Load CalculatorA live converter between watts, kilowatts, BTU/hr, tons of refrigeration and kcal/h, plus CRAC sizing: enter the rack load, see the heat rejection and the recommended unit size with a stated redundancy factor.
- Cabling Pinout & Fiber Polarity ReferenceT568A and T568B side by side as tables and as color-coded strip diagrams, plus crossover and Cisco rollover wiring, PoE Mode A/B pin usage with the 802.3af/at/bt classes, MPO/MTP polarity A/B/C and the copper and fiber Ethernet standards.
- IPv4 Subnet CalculatorNetwork and broadcast address, usable host range, netmask and wildcard mask, host counts and the special-purpose classification for any address and prefix.